Product Code: GFE-MIO
Available In 3-7 Days
The MAINS I/O Modules are fully monitored loop powered devices which permit the interfacing of third-party equipment with the Fire Alarm Control panel using normally open dry contact connections.
The connection to the input is monitored for fault (open or short circuit) and Alarm conditions.
The interface is used to monitor the contacts of an external system which must be interfaced to the Fire Alarm System, for example a Flow Switch in a sprinkler system to indicate if the sprinklers have been activated or extinguishant level monitoring in Gas Extinguishing systems, etc.
Module is provided with a loop short-circuit isolator and with a voltage free single pole change over mains rated output. The output relay is always powered directly from the detection loop. It is not required to use an external 24V DC power supply. Relay operation is confirmed by an onboard red LED.
An 8-way D.I.L. switch is provided to configure the module’s address. This value can be set in the range 1 to 125.
Key Features:
Fast Activation Response
Loop Powered
Five Status LEDs provided
Low Power Consumption
Module features an integral short-circuit loop isolator
Single mains rated relay contact