Product Code: CHQ-DZM(SCI)
In Stock
Model CHQ-DZM(SCI) is a Dual Circuit Zone Controller designed to allow up to 60 conventional detectors (30 on each zone) to be interfaced to Hochiki’s
ESP analogue addressable system. The unit also features a Schottky Diode line continuity option, when used in resistive mode in conjunction with the
optional LCMU.
Full monitoring against malfunction or disconnection, together with a self-test feature through the ESP protocol, ensuring the integrity of the CHQ-DZM(SCI)
at all times. The CHQ-DZM(SCI) utilises simple DIL switches for reliable addressing.
When Zenner Diode EOL option is chosen the conventional zone on the CHQDZM(SCI) does not support any line continuity options, therefore if Call Points
are being interfaced they should be wired at the beginning of the zone.
Features
Single loop address
Requires an auxillary 24 VDC power supply
Provides and supports two independent zones of conventional detectors
Both zones fully monitored for short/open circuit
Also available as DIN
Both models feature an integral SCI
Deeper, glanded IP65 backbox available
Can be used with CHQ-BACKBOX to comply with BS 7671
Approved by LPCB
Marine and SIL2 variants available.